Permit: T05CM03310

Parcel: 106120510

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/25/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/16/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
INSPECTION FOR #1103 ONLY
1. REMOVE STAT WIRES FROM RECEPTACLES AND DISCONNECTS AND MAKE RACEWAY RAIN TIGHT.
2. IDENTIFY SERVICE DISCONNECTS
3. IDENTIFY ALL CKTS IN HOUSE PANEL

UNIT #1103
1. SMOKE DETECTOR WEST BEDROOM TOO CLOSE TO WALL? PROVIDE INSTALLATION INSTRUCTIONS
2. SMOKE DETECTORS EAST BEDROOM NOT WORKING
3. SEAL OPENING IN PANEL
4. NEED COUNTER RECEPTACLE NEXT TO RANGE
5. TRANSFORMER NOT ALLOWED IN CLOSETS
6. PANEL DIRECTORY NOT CORRECT
7. DISHWASHER & MICRO ON SAME CKT
8. PROVIDE PROPER BUSHING/CONNECTOR AT WATER HEATER DISCONNECT.
9. TERMINATE NEUTRAL PROPERLY IN SUB-PANEL
11/15/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*