Permit: T05CM03307

Parcel: 130171470


Addresses:

1655 S ALVERNON WY

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
07/25/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1. MARK DATA PLATE ON AC UNIT WITH PROPER
HEAT STRIP & FUSE ACCORDINGLY
2. PAINT EXPOSED PVC W/LATEX PAINT
3. DO NOT USE GARDEN HOSE FOR COOLER DRAIN
FINISH ELEC. TO COOLER
4. PROVIDE HINGE, KIT FOR EXHAUST FAN AS PER PLANS
5. EXTEND 2 SEWER VENTS 2' ABOVE INTAKES
6. LEFT GAS CARD
7. ALL APPLIANCES MUST FIT UNDER HOOD
03/28/2007 MECHANICAL - ABOVE CEILING Partial Approval SUSPENDED ROUGH DUCT
OK TO INSULATE WITH MIN. R5 DUCT INSULATION
SEAL ALL JOINTS