Permit: T05CM03307

Parcel: 130171470


Addresses:

1655 S ALVERNON WY


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T05CM03307

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/14/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
08/06/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE DRAINS FOR BACKFLOW THAT HAVE DRAINS TO APPROVED RECEPTORS
2) PROVIDE BACTERIA REPORT AS STATED ON 7/16/08 FOR POTABLE WATER
3) PROVIDE MIN 1" AIR GAP PER INDIRECT DRAINAGES ESPECIALLY FROM ICG MACHINE BIN STORAGE
4) SUPPORT INDIRECT DRAIN PIPING
5) COMPLETE DRAINS FOR SODA DISPENSOR TO APPROVED RECEPTOR
6) MAKE ALL FIXTURES WATER TIGHT
7) PROVIDE SEAL AT GREASE TRAP C/O AND LID
8) PROVIDE A TEMPERING VALVE FLOR PUBLIC USE LAVS
07/29/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELED
07/16/2008 PLUMBING - FINAL Partial Approval SEE NOTES ABOVE, PROVIDE BACKFLOW CERTIFICATIONS BACTERIA REPORT FOR POTABLE WATER, CORRECT INDIRECT DRAINAGE CORRECT SANITARY DRAINAGE CONNECTIONS, CORRECT OVERHEAD PIPING SUPPORTS, (BUILDING HAS BEEN REWORKED SINCE 2/17/06, 6/14/07 INSPECTIONS)
04/17/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CALL IN 03050 - HAVE TEST THRU ANSUL VALVE, HAVE ALL GAS APPLIANCES INSTALLED WITH LISTING PLATES AND CORRECTLY SIZE FLEXES TO MEET BTU DEMAND.

1. PROVIDE FLOW CONTROLS FOR ALL FIXTURES TO GREASE WASTE
2. PROVIDE CORRECT DRAINAGE FOR 3-COMP SINK
3. PROVIDE A REVISED CITY APPROVED PLAN OF ACTUAL PLUMBING FIXTURES WHICH ARE INSTALLED OR INSTALL PER PLAN

LIST NOT COMPLETE

4. HAVE PLUMBING CONTRACTOR ON SITE AT NEXT INSPECTION
5. ALL FIXTURES & APPLIANCES NEED TO BE INSTALLED