Permit: T05CM03307

Parcel: 130171470


Addresses:

1655 S ALVERNON WY


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM03307

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/20/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
PLANS AND PERMIT WILL BE REQUIRED FOR
INSTALLING WALK-IN COOLER
11/19/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ALL 15 & 20a 120V KITCHEN RECEPTACLES TO BE GFI
2. ROOFTOP UNIT OVERFUSED
3. EM LIGHTING TO BE ON CIRCUIT IN AREA
4. BOND DUCT HEATER DISCONNECT
5. INSTALL PLASTIC BUSHINGS ON CONNECTORS WITH CONDUCTORS #4 OR LARGER
09/17/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COMPLETE ITEMS ALL ITEMS FROM PREVIOUS INSPECTION.
ELECTRICAL CONTRACTOR TO BE ON SITE FOR INSPECTION
2. COLOR CODING OF WIRES IN PANEL TO BE BLACK, RED, BLUE - A, B, C ARE NEUTRALS BEING SHARED IMPROPERLY
3. DUCT HEATER NOT PER PLAN. CIRCUIT SUPPLYING HEATER AS INSTALLED NOT SIZED LARGE ENOUGH
4. ELECTRICAL CONTRACTOR GO THROUGH ENTIRE JOB INSTALL AS PER PLANS & NEC
5. HAVE APPROVED SET OF PLANS ON SITE
08/29/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION
ON 8/19/08. HAVE APPROVED PLANS ON SITE
2. BOXES MORE THAN 1/4" BACK NEED EXTENSIONS
3. MARK BREAKER NUMBERS. NEED DETAILED PANEL DIRECTORY.
4. INSTALL WALK IN COOLER
5. HAVE PANEL OPEN FOR INSPECTION
6. EM/EXIT LIGHTING NOT WIRED PER PLAN/NEC
7. INSTALL ALL MOUNTING HARDWARE FOR RECEPT IN INDUSTRIAL COVERS
8. NEED GFI RECEPT ON ROOF
9. SECURE DISCONNECTS ON ROOF
10. PROPERLY STRAP SECURE RACEWAYS ON ROOF
11. UNITS MISSING FUSES AND OVERFUSED
12. DISCONNECT NOT GROUNDED
13. EQUIPMENT GROUNDS NOT SIZED PROPERLY
14. ELECTRICAL CONTRACTOR GO THROUGH ENTIRE JOB INSTALL PER PLANS AND NEC.
08/28/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
BUILDING LOCKED NO ONE ON SITE
08/19/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. CONTR. NOT SURE ABOUT PAST INSP. HISTORY CALL INSPECTION
2. SEISMIC WIRES REQUIRED FOR EXITS AND EM LIGHTS
3. PANEL NOT WIRED PER PLAN
4. CANNOT VERIFY FUSE SIZES AT SES
5. 110V RECEPTS IN KITCHEN AREA TO BE GFI PROTECTED PER CODE ALSO SEE PLANS
05/21/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. INSTALL LISTED MAST BRACING
2. INSTALL PROPER SIZE FUSES
3. INSTALL PROPER SIZE EQUIPMENT GROUNDING CONDUCTOR TO PANEL
04/17/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. POST BOND FOR TEMP POWER
2. HAVE PANEL & SWITCH GEAR OPEN FOR INSPECTION
3. INSTALL LISTED MAST BRACING
4. INSTALL DISCONNECT FOR DUCT HEATER
5. RECALL FOR "2065 SERVICE UPGRADE" INSPECTION