Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
Permit Number - T05CM03307
Inspection Description - ELECTRIC - TEMP POWER FOR TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/20/2008 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* | |
05/23/2008 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* | |
05/21/2008 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection :* | |
04/24/2008 | ELECTRIC - TEMP POWER FOR TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL LISTED MAST BRACING 2. MASTS TO BE BONDED PER NEC 250.92 3. MISSING 2ND SET OF PARALLEL FEEDER TO PANEL 4. INSTALL FUSES IN SES 5. JUNCTION BOX NOT SIZED PROPERLY 6. REMOVE HANDLE TO SEE INTO SES 7. GROUND RODS TO HAVE 2/0 SEE PLAN 8. REMOVE MAIN BONDING JUMPER IN PANEL 9. ENSURE LB'S SIZED PROPERLY 10. INSTALL PROTECTIVE BUSHING ON CONDUCTORS #4 OR LARGER 11. GROUND TO PANEL TO BE SIZED FOR 300A - NEC 250.122 12. HAVE ELEC. CONTRACTOR ON SITE FOR NEXT INSPECTION |