Permit: T05CM03307

Parcel: 130171470


Addresses:

1655 S ALVERNON WY


Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Permit Number - T05CM03307

Inspection Description - ELECTRIC - TEMP POWER FOR TEST

Inspection Status - Approved

Date Description Inspector Results Comments
11/20/2008 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection :*
05/23/2008 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
05/21/2008 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :*
04/24/2008 ELECTRIC - TEMP POWER FOR TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL LISTED MAST BRACING
2. MASTS TO BE BONDED PER NEC 250.92
3. MISSING 2ND SET OF PARALLEL FEEDER TO PANEL
4. INSTALL FUSES IN SES
5. JUNCTION BOX NOT SIZED PROPERLY
6. REMOVE HANDLE TO SEE INTO SES
7. GROUND RODS TO HAVE 2/0 SEE PLAN
8. REMOVE MAIN BONDING JUMPER IN PANEL
9. ENSURE LB'S SIZED PROPERLY
10. INSTALL PROTECTIVE BUSHING ON CONDUCTORS #4 OR LARGER
11. GROUND TO PANEL TO BE SIZED FOR 300A - NEC 250.122
12. HAVE ELEC. CONTRACTOR ON SITE FOR NEXT INSPECTION