Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/20/2006 | PLUMBING - INTERMEDIATE | Approved | ||
| 02/02/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* UPSTAIRS CLOSET FLANGE OK FLANGE HAS NOT YET BEEN INSTALLED ON GROUND FLOOR |
|
| 02/01/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CORRECT PITCH ON TRAP ARM 1/4" PER FOOT-NO MORE/NO LESS 2) SECURE WATER PIPING AT TUB AND WC 3) BRASS SCREWS REQUIRED FOR CLOSET FLANGES NOT BRASS COLORED 4) FILL TUB TO FLOOD LEVEL-CHECK FOR LEAK |
|
| 01/31/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*SUPPPORT TUB TRAP ARM USE OF LONG RADIOUS 90 DEGREE REQUIRED AT HORIZONTAL CHANGE OF DIRECTIONS ON TRAP ARMS REVERT ???. USE OF AIR ADMITANCE VALVE ALLOWED ONLY IF SPECIFIED ON P??? SAFETY PLATE MISSING TEST REQUIRED ON TUB WASTE & OVERFLOW 1 1/2 TRAP ARM 42" MAX DEVELOPED LENGHT CLOSET FLANGES TO BE SECURED W/ BRASS SCREWS. |