Permit: T05CM03283

Parcel: 12006221B

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/08/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
03/05/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
T-TOP SCREENS NOT CORRECT
02/28/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
MAKE ALL CORRECTIONS FROM PREVIOUS NOTES
02/27/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE ROOF JACKS AT ALL ROOF PENETRATIONS.
2. PAINT EXPOSED PVC WITH LATEX PAINT & SUPPORT
EVERY 4'
3. PERMANENTLY MARK UNIT DATA PLATE WITH THE PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY. UNIT 1 FUSES CANNOT BE IDENTIFIED.
4. SECURE THE ELEC. CONDUITS. TIGHTEN LOOSE FITTINGS.
5. REMOVE SCREEN FROM DRYER VENT T-TOPS
BE SURE ALL EXHAUST T-TOPS HAVE SCREEN.