Permit: T05CM03282

Parcel: 12006221B

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/05/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
T-TOP SCREENS NOT CORRECT
02/28/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
MAKE ALL CORRECTIONS FROM PREVIOUS NOTES
02/27/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE ROOF JACKS AT ROOF PENETRATIONS
2. PAINT EXPOSED PVC WITH LATEX PAINT & SUPPORT
EVERY 4'
3. PERMANENTLY MARK UNIT DATA PLATE WITH THE PROPER HEAT STRIP & FUSE ACCORDINGLY. USE FUSES THAT CAN BE IDENTIFIED.
4. SECURE ELEC. CONDUITS UNIT 2 NOT CONNECTED PROPERLY. TIGHTEN LOOSE FITTINGS.
5. REMOVE SCREEN FROM DRYER VENT T-TOPS
PROVIDE SCREEN IN EXHAUST FAN T-TOPS