Permit: T05CM03282

Parcel: 12006221B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/13/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/12/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL BOX EXTENDERS IN CABINET RECEPTACLES
2. BEDROOMS NOT WIRED TO ARC FAULT BREAKERS PROPERLY
3. OUTSIDE FIXTURES NOT INSTALLED
02/28/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
02/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. DO NOT DOUBLE LUG GROUNDS IN PANEL TO GROUND ONE SERVICE TO ANOTHER, USE SPLIT BOLT BELOW PANEL.
2. INSTALL PERMANENT ADDRESS LABELS ON SERVICES MARKING PEN NOT APPROVED.
3. STRAP #4 TO WALL
4. BE ADVISED THAT ARC FAULT CIRCUIT BREAKERS ARE REQUIRED FOR ALL OUTLETS IN BEDROOMS PER NEC ALSO, 2 GFI PROTECTED CIRCUITS ARE REQUIRED FOR KITCHEN COUNTER TOP RECEPTS PER NEC
5. DISCONNECTS REQUIRED FOR WATER HEATERS

COULD NOT LOCATE PLANS/PERMIT?