Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/23/2007 | MECHANICAL - FINAL | Approved | OK FOR FINAL | |
| 03/21/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* I.D UNITS PROVIDE ADEQUATE SIZE GAS FLEX CONNECTORS SECURE ELEC. CONDUITS BLDG. INSPECTOR CAN SIGN OFF |
|
| 03/19/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 3/8" I.D X 36" GAS FLEX NOT ADEQUATE FOR 108,000 BTU 2. A/C UNITS NOT LEVEL 3. PROVIDE FRESH AIR INTAKES 4. CONDENSATE CANNOT TERMINATE INTO A SEWER VENT 5. PERMANENTLY I.D UNITS & DISCONNECTS 6. SECURE ELEC. CONDUITS 7. NO CONTRACTOR ON SITE NO PLANS. |