Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T05CM03259
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/12/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
03/09/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CONTRACTOR CANCELLED |
|
02/14/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. YARDWATER TRACER WIRE AND TEST OK 2. PROVIDE VACUUM BREAKERS FOR ALL HOSE BIBS 3. REPAIR LEAK ON HOSE BIB AT NORTH END OF BUILDING. |
|
02/12/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE APPROVED PLANS FOR TANKLESS WATER HEATERS. 2. PROVIDE TRACER WIRE ON PVC YARD WATER PIPING 3. PROVIDE VACUUM BREAKERS ON ALL HOSE BIBBS. 4. PROVIDE BACKFLOW PREVENTOR FOR YARD WATER. |
|
01/26/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CALLED FOR YARDWATER PIPING NOT UNDER TEST |
|
01/17/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CONDENSATE IN WALL OK |
|
12/18/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PER ALTERNATE # TO TAKE OUT WATER HEATER AND INSTALL TANKLESS WATER HEATER. 2. PROVIDE APPROVED PLANS |
|
12/11/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. APPROVED PLANS HAVE WATER HEATERS IN EACH UNIT PIPING FOR WATER HEATERS NOT IN |