Permit: T05CM03259

Parcel: 13706132A


Addresses:

5433 S 12TH AV


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T05CM03259

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/12/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
03/09/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELLED
02/14/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. YARDWATER TRACER WIRE AND TEST OK
2. PROVIDE VACUUM BREAKERS FOR ALL HOSE BIBS
3. REPAIR LEAK ON HOSE BIB AT NORTH END OF BUILDING.
02/12/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. PROVIDE APPROVED PLANS FOR TANKLESS WATER HEATERS.
2. PROVIDE TRACER WIRE ON PVC YARD WATER PIPING
3. PROVIDE VACUUM BREAKERS ON ALL HOSE BIBBS.
4. PROVIDE BACKFLOW PREVENTOR FOR YARD WATER.
01/26/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CALLED FOR YARDWATER PIPING NOT UNDER TEST
01/17/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CONDENSATE IN WALL OK
12/18/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PER ALTERNATE # TO TAKE OUT WATER HEATER AND INSTALL TANKLESS WATER HEATER.
2. PROVIDE APPROVED PLANS
12/11/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. APPROVED PLANS HAVE WATER HEATERS IN EACH UNIT
PIPING FOR WATER HEATERS NOT IN