Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05CM03259
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/20/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
03/19/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. BOND SCREWS MISSING ON #1 & #5 DISCONNECTS AT SERVICE. 2. BOND GAS PIPING 3. BOND BUSHINGS IN GUTTER NOT TO BE DAISY CHAINED IF SO, YOU MUST SIZE THE BOND WIRE. 4. INSTALL W/P COVERS FOR SIGN BOXES. |
|
03/15/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. COMPLETE TERMINATIONS AT SERVICE, INSTALL BOND BUSHING WHERE REQUIRED AHEAD OF OVERCURRENT AT SERVICE. OK PANEL TERMINATIONS INSIDE SPACES. 2. BOND WATER PIPING |
|
03/08/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. A WAIVER FOR OVERHEAD SERVICE WILL BE REQUIRED PER CITY ORDINANCE. 2. OK UNDERGROUND CONDUITS, FEEDERS, NO GROUNDING YET. |
|
02/12/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ABOVE CEILING GRID |
|
01/23/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK SOFFITS, PROVIDE LETTER FROM ARCH. FOR MC USE APPROVAL |
|
12/21/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | OK WALLS |