Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 07/15/2005 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* LOCKED BOTH FRONT & BACK |
|
| 07/12/2005 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TIE OFF AND SUPPORT ALL MC CABLE HANGING OUT OF WALLS. 2. SUPPORT EMT ON SWITCH BY BATH ROOM DOOR WITH IN 3' OF SWITCH. 3. FOR ABOVE CEILING INSPECTION MAKE UP AND CLOSE ALL JUNCTION BOXES. 4. RUN MC CABLE INTO WALLS ON WEST SIDE INTALL CUT IN BOXES AND GROUND BOXES. 5. INSTALL PLASTER RING ON BOX CORRECTLY BACK ROOM. |