Permit: T05CM03221

Parcel: 140383270

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
12/15/2005 FRAMING Approved IVRS - Inspection :*
12/07/2005 FRAMING Partial Approval IVRS - Inspection :*
1) OK TO INSULATE
2) ACCESS TO FURNACE BLOCKED-PROVIDE 30" VERTICAL ACCESS
3) DUCT WORK KINKED AT UNIT-PROVIDE 1 DUCT DIAMETER RADIUS
12/02/2005 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) RED HEAD ANCHOR BOLTS LOOSE
2) NO DWV WATER TEST
3) ACCESS TO FURNACE BLOCKED BY DUCT WORK. PROVIDE 30" VERTICAL CLEARANCE
4) DUCT WORK NOT COMPLETE
5) BEDROOM SHEARWALL REQUIRES ANCHOR BOLTS AT 48" ON CENTER
6) ELECTRIC BOX AND WIRE DAMAGED MASTER BEDROOM
7) FIRE STOP REQUIRES 2 LAYERS 1/2" OSB
8) LTT 20 B MISSING EPOXY BOLT 2 EACH
9) STOPPED INSPECTION-TOO MANY ITEMS