Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/15/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 12/07/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) OK TO INSULATE 2) ACCESS TO FURNACE BLOCKED-PROVIDE 30" VERTICAL ACCESS 3) DUCT WORK KINKED AT UNIT-PROVIDE 1 DUCT DIAMETER RADIUS |
|
| 12/02/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) RED HEAD ANCHOR BOLTS LOOSE 2) NO DWV WATER TEST 3) ACCESS TO FURNACE BLOCKED BY DUCT WORK. PROVIDE 30" VERTICAL CLEARANCE 4) DUCT WORK NOT COMPLETE 5) BEDROOM SHEARWALL REQUIRES ANCHOR BOLTS AT 48" ON CENTER 6) ELECTRIC BOX AND WIRE DAMAGED MASTER BEDROOM 7) FIRE STOP REQUIRES 2 LAYERS 1/2" OSB 8) LTT 20 B MISSING EPOXY BOLT 2 EACH 9) STOPPED INSPECTION-TOO MANY ITEMS |