Permit: T05CM03163

Parcel: 10821328B

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T05CM03163

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/22/2005 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
1) CORRECTION MADE
2) NEED TO VIEW PERM CAP ON TEST WYE ON 2ND FLOOR CEILING SPACE FOR FINAL
07/21/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) H20 PIPING OK
2) 6 PSI AIR TEST ON 2" DRAIN OK
3) OK TO COVER WALL
4) NEED TO SEE PIPING ON 2ND FLOOR CEILING SPACE CONNECTION FOR DRAIN AND VENT TIE IN THIS SPACE
07/20/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROVIDE LONG RADIUS DRAINAGE FITTING FOR DRAIN
2) WATER OR AIR TEST DRAINAGE PIPING
3) FIRE SEAL FLOOR PENETRATION
4) H20 PIPING OK
5) ALL DEMO AREA OK
6) ITEM 3005 NOT REQUIRED PER PAPERWORK TURNED IN BY INSPECTOR R. RICH
07/19/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) CAP OFF DRAIN PIPING IN CONFERENCE ROOM OK
2) PROVIDE PERM CAP FOR 3/4 H20 TO WATER HEATER THAT IS ?
3) CAP OK FOR DRAIN IN OFFICE 122/H20 PIPING IS REMOVED
4) PROVIDE PERM CAP FOR VENT ABOVE CEILING IN OFFICE 122