Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/17/2006 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
| 03/08/2006 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* CHECK WELDS ON GREASE DUCTS. REMOVE SCREWS FROM DUCTS & WELD HOLES. BE SURE FIRE DAMPERS ON HOOD HAVE ACCESS. |
|
| 03/07/2006 | MECHANICAL - HOODS | Denied | IVRS - Inspection : See detailed listing on site.| 999* COULD NOT COMPLETE THE INSPECTION. THERE IS COMBUSTIBLE MATERIAL (FRP) WITHIN 18" OF THE TYPE 1 HOODS. IMC DOES NOT ALLOW THIS CONTRACTOR SAID DAVE MANN SAID IT WAS OK. HE ASKED ME NOT TO DO THE INSPECTIONS AND THAT DAVE MANN WILL DO THE FOLLOW UP INSPECTIONS. |