Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/06/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/23/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TCO SUBJECT TO OTHER INSPECTIONS 1. WRITING OF REVISIONS FOR OUTDOOR LIGHTING |
|
| 03/22/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. WE HAVE CONDUCTOR OVER FILL IN BOXES ON TOP OF MARKING BOX 2. USE A NON COMBUSTIBLE PRODUCT FOR FILL 3. PLEASE VERIFY LISTING FOR FITTINGS OF SEAL TITE & TIGHTEN LOOSE FITTINGS. 4. CONDUCTORS LARGER THAN #8 TO HAVE PROTECTION AT FITTINGS. 5. MINIMUM GROUND CONDUCTOR SIZE FOR SATELLITE IS #10 810.21 ALSO SUPPORT CABLE OFF ROOF. 6. FILL UNUSED OPENING IN DISCONNET 7. PLEASE VERIFY LISTING FOR SODA DISPENSER. 8. WHERE IS FIXTURE "F" IN OUTDOOR LIGHTING CALCULATIONS. NEED REVISION OF FIXTURE FOR DELETED POLE LIGHT PER OUTDOOR LIGHTING ORDINANCE. |