Permit: T05CM03161

Parcel: 11449042Q


Addresses:

2400 N PANTANO RD

Inspection Status: Approved

Inspection History: BUILDING PRE-SLAB

Date Description Inspector Results Comments
09/19/2007 BUILDING PRE-SLAB Approved
12/09/2005 BUILDING PRE-SLAB Partial Approval
12/07/2005 BUILDING PRE-SLAB Not ready for Inspection IVRS - Inspection :*#4 DOWELS MUST EXTEND 4' INTO SLAB PER DETAILS 103,104,ON SHEET S 4
F5 COLUMN FOOTING @ S.SIDE OF BUILDING MUST BE 24" IN DEPTH.
PROVIDE ADDITIONAL # 4 VERTICAL DOWERS ON EACH SIDE OF HOLDOWNS PER DETAIL 21 + 25 ON SHEET S1.2
HD10A HOLDODWNS MUST BE IN PLACE & SECURE PRIOR TO PLACEMENT OF CONCRETE.
NEED TO LEAVE PERMIT & CARD ON SITE.
NEED PAD CERTIFICATION FROM SURVERYOR TO VERIFY SET BACKS.