Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T05CM03160
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2005 | BUILDING - FINAL | Approved | ||
| 08/24/2005 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1) STRUCTURAL AND EGRESS COMPLETE, CHAP 11 ACCESSIBILTY OK 2) BUILDING FINAL MAY APPROVED BY ELECTRICAL INSPECTOR WHEN ELECTRICAL IS COMPLETED |
|
| 08/23/2005 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) FINISH ALL DOOR HARDWARE 2) PROVIDE FINAL INSPECTION REPORTS FROM MECHANICAL, ELECTRICAL AND PLUMBING INSPECTORS 3) VERTICAL GRAB BAR IN MENS ROOM TO BE 40" FROM BACK WALL 4) CALL BETH AT 791-5550 X 1171 AND MAKE SURE YOU DON'T NEED ANY FIRE C OF O INSPECTIONS |
|
| 08/17/2005 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SHOWER INSTALLATION MUST MEET IBC CHAPTER 11 REQUIREMENTS FOR ACCESSIBILITY (1109.2) YOUR CURRENT PREFAB UNIT DOES NOT MEET THESE STANDARDS |