Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T05CM03131
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/14/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
02/07/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING RETRO H.D. AT GARAGE FRONT (DO NOT COVER) |
|
10/19/2005 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) OK TO DRY IN 2) GARAGE FRONT HOLDOWN EAST END OF WEST CORNER SPAULLED 2) PROVIDE ENGINEER AND CITY OF TUCSON APPROVED REPAIR |
|
10/13/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL RETRO FIT APPROVED EPOXIED SPECIAL INSPECTED HOLDOWNS AT EXCESSIVELY SPALLED HOLDOWNS 2) SHEARWALL 6 NAILING 4"-12" NAILING PATTERN INCOMPLETE 3) REINSTALL CONDUIT INTO WALL WEST SIDE 4) WIND BRACING MISSING WEST SIDE MAX 25' OF RUN AND EAST SIDE 5) NAILS SET TO DEEP EXTERIOR SHEARWALLS-RENAIL 6) SHEAR PANEL REAR TO CARRY TO WINDOW AND DOORS 7) HOLDOWNS WRONG LOCATIONS 8) NO LADDER IN INSPECT ROOF 9) STOPPED INSPECTION |