Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/05/2006 | FRAMING | Approved | IVRS - Inspection :* | |
11/02/2005 | FRAMING | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection Mechanical plan specifies gas furnace . No gas installed House is all electric plan specifies gas. Have plans revision to as built and approved by City of Tucson Mechanical, Electric and Plumbing not per approved plan. Build to plan or revise to as built You must pay a reinspection fee |
|
10/27/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FLEX DUCT CANNOT BE INSTALLED IN GARAGE MUST USE 26G METAL 2) 3/8" OSB SHEAR PANELS MUST BE INSTALLED WITH LING DIEMENSION ACROSS STUDS PER IRC R602.3(3) NOTE 3) 10 DT1 NOT COMPLIED WITH AT GARAGE SHEAR BLOCK NAIL AND H2.5 CLIPS MISSING 4) PLUMBING PLAN REQUIRES KITCHEN SINK TO VENT TO ROOF 5) BUILD TO PLAN OR REVISE PLAN TO AS BUILT 6) A/C CONDENSATE OUTSIDE OF WALL 7) HOLDOWNS NUTS LOOSE 8) HALL BATH TRAP WEIR CANNOT BE HIGHER THAN VENT OPENING 9) HAVE PLAN REVISED TO DELETE GAS AND ADD ELECTRIC ONLY 10) REVISE MECHANICAL PLAN TO DELETE GAS FURNACE 11) STOPPED INSPECTION-TO MANY ITEMS |