Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM03124
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/04/2007 | FRAMING | Approved | IVRS - Inspection :* | |
04/03/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FIREBLOCKS MISSING @ MECH. DROP CEILING 2. ANCHOR BOLTS MISSING @ PLATE JOINTS 3. ANCHOR BOLTS LOOSE 4. VENT GAS SLEEVE IN CONCRETE @ GRADE LEVEL 5. REFEE WILL APPLY |
|
03/30/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FIRE STOP ALL PENETRATIONS THROUGH TOP PLATES 2) ANCHOR BOLT MISSING AT PLATE JOINT IN GARAGE AND THROUGHOUT 3) BLOCK REGISTER IN STORAGE 4) VACUUM BREAKERS REQUIRED ON HOSE BIBS 5) FIREBLOCKS MISSING THROUGHOUT 6) STOPPED INSPECTION 7) REFEE WILL APPLY |
|
03/22/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FIRE BLOCK AT HUTCH CHASE BY FIREPLACE BROKEN REPLACE 2) FIRESTOP AT GARAGE OPENING CHASE 3) FIRESTOP AT ALL OVERSIZED HOLES IN FIREBLOCK NOT COMPLETE AT CHIMNEY 4) SHEARWALL AT GARAGE HAS BEEN CUT NEED TO REPLACE 5) FIRE BLOCKING BEDROOM #2 6) NO DWV TEST 7) GAS PRESSURE TEST OK 8) FIRESTOP MISSING THROUGHOUT HOME 9) NEED PROTECTION PLATE ON ALL PLUMBING WITH IN 1.5" AT BATH TO BEDROOM #2 & #3 |