Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T05CM03098
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/24/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
10/25/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) MISSING EXIT SIGN BOX FOR ENTRY 2) NO FIXTURE IN CLASSROOM #3, WILL SPRINKLER RISER BE MOVED TO ALLOW FIXTURE TO SET IN, ALSO MUST BE SCREWED TO ? 3) NEC 800-6 FOR COMMUNICATIONS CIRCUITS REQUIRES INSTALLER TO HANG BY STRAPS STAPLES OR HANGERS OR SIMILAR FITTINGS NOT JUST TO BE ? ABOVE CEILING 4) OK TO COVER AREAS NOT AFFECTED-LEAVE OTHER AREAS OPEN |
|
08/15/2005 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |