Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/29/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/05/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) ROMEX NEEDS TO BE STAPLED AS PER LAST INSPECTION NOTE |
|
| 08/03/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) MUST SUPPORT CABLES WITHIN 12' ABOVE AND BELOW BREAKER PANEL, RE-CALL INSPECTION WHEN DONE |