Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/17/2006 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 01/13/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL STEALTH VENTS 2) SCREW MISSING IN DEAD FRONT COVER 3) WHITE CONDUCTOR MUST BE TAPED BLACK WHEN USED AS HOT 4) A/C UNIT IN FRONT OF DISCONNECT 5) FIXTURES AT LANDING MUST BE 6'-8" OFF FLOOR 6) OUTLTE UNDER WINDOW IN BED 2 NOT FUNCTIONAL 7) GAS LINE AT FURNACE MUST BE SECURED 8) HANDRAIL NOT COMPLETE |