Permit: T05CM03075

Parcel: 141017920


Addresses:

6007 S CEDAR ELM LN


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T05CM03075

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
11/01/2005 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
09/30/2005 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection 1) NOT READY SEE LAST INSPECTION
09/28/2005 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) ADD STRAPS PER REVISION FRONT AND REAR 2ND FLOOR TO BEAM
09/23/2005 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) NEED ONE WIND BRACE AT EAST AND ONE AT WEST SIDE
2) LAG DETAIL TYING
3) SHEAR TO BEAM, AT FRONT 2ND FLOOR SHEAR
09/15/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONTINUE SHEAR UP TO FLR WEST SIDE 10'
2) NEED BELLY BAND
3) ATTACH SHEAR WALLS TOP AND BOTTOM
4) WIND BRACE NAIL MISSING EAST
5) NAIL SHEAR PANELS TO ROOF
6) NAIL ALL FRIELE BLKS TO ROOF
7) RAT RUNS
8) MISSING 4' PANEL AT WEST SIDE GARAGE
9) LTF4'S AT GABLE TO SHEAR
10) STRAP STUDS AT FRONT POP OUT