Permit: T05CM03034

Parcel: 125100670


Addresses:

3711 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T05CM03034

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
04/20/2007 PLUMBING - GAS PRESSURE TEST Approved PER PL FINAL
04/11/2007 PLUMBING - GAS PRESSURE TEST Partial Approval REVISED PLAN NOT PROVIDED
MECHANICAL INSPECTIONS NEEDED
SUPPORT GAS SERVICE W/PIPE CLAMP
REMOVE CONCRETE FROM PIPE USE NON-SHRINK MASTIC PER CODE.
02/01/2007 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
01/19/2007 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
12/21/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1. YOU DID NOT CALL FOR PRE-SLAB INSPECTION.
2. MOST PIPES HAVE FOAM PROTECTION VISIBLE
3. ANY PIPES THAT DO NOT, WILL HAVE TO BE EXPOSED AND WRAPPED W/FOAM WHERE PASSING THROUGH CONCRETE.
4. MISSION COUPLINGS ARE REQUIRED AT PL TO C1 TRANSITIONS.
5. EXPOSE MISSION COUPLING AT ONE LOCATION BELOW SLAB TO VERIFY.
6. SUPPORT OVERHEAD PLASTIC AT 4' INTERVALS.
7. DRAINAGE FITTINGS ON RD'S
8. TEST OK ON ALL 1ST FLOOR RD'S EXCEPT AT CORRECTION OK.
9. REMOVE EXCESS FLUX W/DAMP RAG PER UPC INSTALLATION STANDARDS.
10. HAMMER ARRESTORS REQUIRED AT QUICK CLOSING VALVES.
11. PROVIDE APPROVED REVISED PLANS FOR GAS AND WATER
12. PROVIDE SPEC FOR GALV
13. CALL FOR INTERMEDIATE INSPECTION WHEN READY