Permit: T05CM03034

Parcel: 125100670


Addresses:

3711 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM03034

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/25/2007 ELECTRIC - FINAL Approved
04/23/2007 ELECTRIC - FINAL Partial Approval OK TEMP C OF O
AT TRASH COMPACTOR STRUCTURE
1. USE DIRECT BURIAL RATED CLAMPS/ACORNS FOR GROUND RODS
2. USE PROPER BOX EXTENSIONS IN WALLS
3. PROPERLY GROUND ALL BOXES
4. REMOVE UNUSED BRANCH CKT
5. COMPACTOR NOT IN YET
6. IDENTIFY PHASE CONDUCTORS

EXTERIOR
1. FINISH IDENTIFICATION OF BRANCH CKT'S AT PANEL.

ON ROOF
1. GROUNDS #6 AND SMALLER TO BE GREEN OR BARE ENTIRE LENGTH
2. INSTALL PROPER SIZE FUSES -- AC #4
3. PROPERLY GROUND J-BOX (SCRUBBER & AC DISCONNECT)
4. PROPERLY IDENTIFY PANEL "C" SCHEDULE

INSIDE:
1. MAKE SURE ALL CKTS IN ALL PANEL DIRECTORY'S ARE CORRECTLY IDENTIFIED

OK TEMP C OF O
04/20/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WORK IN PROGRESS
04/19/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
04/17/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WORK IS IN PROGRESS AND IS NOT READY FOR FINAL INSPECTION. PLEASE DO NOT CALL FOR FINAL BEFORE
ALL WORK IS COMPLETE, FULLY FUNCTIONAL,
CLOSED UP AND PER PLAN