Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - OUTDOOR LIGHTING
Permit Number - T05CM03034
Inspection Description - ELECTRIC - OUTDOOR LIGHTING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/25/2007 | ELECTRIC - OUTDOOR LIGHTING | Approved | ||
04/06/2007 | ELECTRIC - OUTDOOR LIGHTING | Partial Approval | IVRS - Inspection :* 1) OK 3 LIGHT POLE BASES 2) NEED TO POST BOND FOR TEMP POWER TO TEST 3) NEED LETTER OF TORQUE 4) BOND GAS PIPE 5) IDENTIFY CONDUCTORS PER NEC 6) CANNOT CONNECT GROUND WITH SHEET METAL SCREWS-NEC 250.8 7) CONNECT GROUNDS TO GROUND/NEUTRAL BAR AT SES OR REMOVE PAINT AT CONNECTIONS PER NEC 250.12 |
|
04/05/2007 | ELECTRIC - OUTDOOR LIGHTING | Not ready for Inspection | IVRS - Inspection :* INSTALL SUPPLEMENTARY GROUNDING IN POLE BASE PER PLAN E-1 |