Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T05CM03034
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/25/2007 | ELECTRIC - ABOVE CEILING | Approved | ||
01/10/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
01/09/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. RACEWAYS TO BE COMPLETE RUNS FROM BOX TO BOX WITH PROPER CONNECTORS AND LOCKNUTS INTO BOXES - NEC 300.18, 352.46 2. GO THROUGH ALL METAL BOXES AND MAKE SURE THEY ARE PROPERLY GROUNDED - NEC 110, TIGHTEN SCREWSM, NO INSULATION UNDER SCREW, NO STRANDED WIRE, ETC. 3. HAVE OVERFILLED J-BOXES - NEC 314.16 4. GAS, SPRINKLER PIPES TO BE BONDED - NEC 250.104 5. SHEETMETAL SCREWS NOT ALLOWED FOR GROUND CONNECTION -- NEC 250.8 |
|
01/05/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. GROUND METAL BOXES 2. PROTECT FLEX CONDUIT AT STUDS & PLATES 3. SUPPORT FLEX CONDUIT 12" OF BOXES & CANS 4. USE APPROVED COLORS FOR CONDUCTORS - CITY AMENDMENTS 310.5 5. SUPPORT CONDUITS AS PER CODE 6. PREVENT DIELECTRIC CONTACT 7. FINISH #2, #3 PREVIOUS INSPECTION 8. FINISH ELECTRIC AND VDV WIRING |
|
12/29/2006 | ELECTRIC - ABOVE CEILING | Cancelled | IVRS - RI canceled |