Permit: T05CM03034

Parcel: 125100670


Addresses:

3711 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM03034

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/25/2007 ELECTRIC - ABOVE CEILING Approved
01/10/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
01/09/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. RACEWAYS TO BE COMPLETE RUNS FROM BOX TO BOX WITH PROPER CONNECTORS AND LOCKNUTS INTO BOXES -
NEC 300.18, 352.46
2. GO THROUGH ALL METAL BOXES AND MAKE SURE THEY ARE PROPERLY GROUNDED - NEC 110, TIGHTEN SCREWSM, NO INSULATION UNDER SCREW, NO STRANDED WIRE, ETC.
3. HAVE OVERFILLED J-BOXES - NEC 314.16
4. GAS, SPRINKLER PIPES TO BE BONDED - NEC 250.104
5. SHEETMETAL SCREWS NOT ALLOWED FOR GROUND CONNECTION -- NEC 250.8
01/05/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. GROUND METAL BOXES
2. PROTECT FLEX CONDUIT AT STUDS & PLATES
3. SUPPORT FLEX CONDUIT 12" OF BOXES & CANS
4. USE APPROVED COLORS FOR CONDUCTORS - CITY AMENDMENTS 310.5
5. SUPPORT CONDUITS AS PER CODE
6. PREVENT DIELECTRIC CONTACT
7. FINISH #2, #3 PREVIOUS INSPECTION
8. FINISH ELECTRIC AND VDV WIRING
12/29/2006 ELECTRIC - ABOVE CEILING Cancelled IVRS - RI canceled