Permit: T05CM03027

Parcel: 14115008T

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
12/21/2005 MECHANICAL - ABOVE CEILING Approved PER MECH FINAL
12/14/2005 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*COMBUSTIBLES NOT ALLOWED WITHIN 18" OF TYPE I HOOD SEE SECTION 507.9 2000 IMC.
OK FOR CEILING TILES DINING AREA ONLY
NON CANOPY HOOD CANNOT EXCEED 3' FROM THE COOKING SURFACE TO THE INTAKE ON THE HOOD