Permit: T05CM03027

Parcel: 14115008T

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T05CM03027

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/29/2005 PLUMBING - FINAL Approved IVRS - Inspection :*
CORRECT TRAP FOR INDIRECT DRAIN FROM ICE MACHINE.
SEC. 803 OF THE UPC REQUIRES THAT INDIRECT WASTE PIPES EXCEEDING 5 SHALL BE DIRECTLY TRAPPED.
REVIEWED CHANGE OF MECHANICAL DRAWING.
RECEIVED
BACKFLOW CERTS (5)
LETTER FROM ARCHITECTS ON HOOD REVISION
3 STAMPED CUT SHEETS FOR TYPE 2 HOOD
12/27/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*A COMBINATION WYE & 1/8" BOND FITTING IS REQUIRED FOR CLEANOUT FITTING ON DISH WASHER
ICE MAKER INDIRECT WASTE REQUERIES A DIRECT TRAP & VENT
INDIRECT DRAIN ON SINKS REQUIRES SUPPORT
AIR GAPS ARE REQUIRED TO BE TWICE THE EFFECTIVE OPENING.
PROVIDE ANSEL VALVE LOCATION TAG ON CEILING GRID.
PLEASE PROVIDE COPIES PAPER WORK FOR OVER HOOOD & BACKFLOW CERTS.
12/22/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
FINISH ITEMS LISTED ABOVE THEN CALL FOR INSPECTION, SHEET M1 DELEGATES ITEM #9
12/20/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE DOUBLE CHECK VALVE ASSEMBLY TO EACH APPLIANCE - COFFEE & TEA MAKER
2. TERMINATE DRAIN FROM HOT TABLE
3. PROVIDE BACKFLOW CERTIFICATIONS
4. TERMINATE ALL INDIRECT DRAINS CORRECTLY.
5. PROVIDE LONG RADIUS DRAINAGE FITTINGS WITH CLEANOUT FOR OUR 135 DEGREE CHANGE OF DIRECTION ON INDIRECT DRAINAGE WITH SUPPORT WHERE REQUIRED.
6. PROVIDE CORRECT DRAINAGE FOR ICE MACHINE & BIN
7. HAVE ALL APPLIANCES CONNECTED.
8. PROVIDE INSULATION ON WATER PIPING FOR APPROVED PLAN.
9. PROVIDE CITY APPROVED PLAN FOR DELVATION OF ANSUL VALVE TO EVEN.
12/19/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*