Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESS TEST FNL
Permit Number - T05CM03027
Inspection Description - PLUMBING - GAS PRESS TEST FNL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/19/2005 | PLUMBING - GAS PRESS TEST FNL | Approved | IVRS - Inspection :*OK FOR GAS CARD TYPE II GAS HOOD INSTALLED PER PLAN REVISION PROTECT EXPOSED PLASTIC PIPING ON ROOF BACKFLOW CERTS. |
|
| 12/16/2005 | PLUMBING - GAS PRESS TEST FNL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE REVISED APPROVED PLAN BY CITY DELEGATING ANSUL VALVE TO PIZZA OVEN |
|
| 12/12/2005 | PLUMBING - GAS PRESS TEST FNL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. READ NOTICE ON SIDE OF OVEN & COMPLY WITH GAS CONNECTION AND SAFETY CABLES INSTALLATION 2. PROVIDE CORRECT LISTED FLEX FOR BTU REQUIREMENTS OF WATER HEATER 3. PROVIDE CONNECTION TO ANSUL VALVE FOR PULL STATION 4. PROVIDE SAFETY CABLES FOR FRYER 5. PROVIDE ACCESS TO ROOFTOP VENTS (DOOR LOCKED) 6. HAVE APPROVED PLAN ON SITE |
|
| 12/02/2005 | PLUMBING - GAS PRESS TEST FNL | Not ready for Inspection | IVRS - Inspection :*NOT READY |