Permit: T05CM03027

Parcel: 14115008T

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESS TEST FNL

Permit Number - T05CM03027

Inspection Description - PLUMBING - GAS PRESS TEST FNL

Inspection Status - Approved

Date Description Inspector Results Comments
12/19/2005 PLUMBING - GAS PRESS TEST FNL Approved IVRS - Inspection :*OK FOR GAS CARD
TYPE II GAS HOOD INSTALLED PER PLAN REVISION
PROTECT EXPOSED PLASTIC PIPING ON ROOF
BACKFLOW CERTS.
12/16/2005 PLUMBING - GAS PRESS TEST FNL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE REVISED APPROVED PLAN BY CITY DELEGATING ANSUL VALVE TO PIZZA OVEN
12/12/2005 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. READ NOTICE ON SIDE OF OVEN & COMPLY WITH GAS CONNECTION AND SAFETY CABLES INSTALLATION
2. PROVIDE CORRECT LISTED FLEX FOR BTU REQUIREMENTS OF WATER HEATER
3. PROVIDE CONNECTION TO ANSUL VALVE FOR PULL STATION
4. PROVIDE SAFETY CABLES FOR FRYER
5. PROVIDE ACCESS TO ROOFTOP VENTS (DOOR LOCKED)
6. HAVE APPROVED PLAN ON SITE
12/02/2005 PLUMBING - GAS PRESS TEST FNL Not ready for Inspection IVRS - Inspection :*NOT READY