Permit: T05CM03018

Parcel: 11711080B


Addresses:

125 E PENNINGTON ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/27/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
THIS INSPECTION IS APPROVED BASED ON LETTER SUPPLIED BY ELECTRICAL CONTRACTOR, WHO CERTIFIED WORK DONE BY PREVIOUS CONTRACTOR THAT NEVER HAD INSPECTIONS AND COVERED WORK. LETTER FROM MEHL ELECTRIC WAS PROVIDED TO ME TODAY 3/27/06
03/24/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/13/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
HAVE A QUALIFIED ELECTRICIAN GO THROUGH ALL WORK AND CORRECT ALL CODE VIOLATIONS WHEN ELECTRICIAN IS FINISHED CALL IN FOR INSPECTION AND HAVE ALL EQUIPMENT OPEN AND ACCESSIBLE. ALSO, NEED TO PAY RE-INSPECTION FEE PRIOR TO NEXT INSPECTION.
14 GA WIRE ON 20 AMP CKT.
INCORRECT CONDUCTOR TERMINATIONS
INCORRECT RACEWAY TERMINATIONS
RACEWAYS NOT SECURED/SUPPORTED
CONDUCTORS NOT IDENTIFIED
GROUNDS NOT PROPERLY TERMINATED
ETC, ETC.
03/07/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. MAKE CORRECTIONS FROM PREVIOUS INSPECTION
03/06/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COULD NOT LOCATE PERSONAL-PLANS/PERMIT ?
03/03/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER ANGEL-WILL RESCHEDULE
02/22/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*HAVE EQUIPMENT OPEN VERIFY WIRING IS PER PLAN MAKE SURE PANEL DIRECTORIES ARE MARKED
02/21/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*WILL CALL TO RE SCHEDULE PER MY REQUEST
02/10/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HAVE THE ORIGINAL ELECTRICIAN ON SITE FOR INSPECTION
2. HAVE EQUIPMENT ACCESSIBLE FOR INSPECTION