Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/09/2005 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/10/2005 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :*SEE MECH SPEC'S & NOTES # 9 & 10 NEW FLEX DUCT HAS TO BE EQUAL TO R-5. WRAP ALL OLD HARD DUCT. 90 DEGREE ELBOWS THAT ARE UNINSULATED BLOCK ALL OPENINGS IN ROOF THAT ALLOW HOT INFILTRATION OF AIR BELOW THE BUILDING INSUL. ENVELOPE ALL PC'S HARD DUCT, RETURN CAN'S, ETC, NEED SEISMIC STRAPS OR WIRE TO SECURE IN POSITION. |