Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T05CM03005
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/04/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
08/30/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
08/29/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FINISH INSTALLING DEVICES AND PLATES 2) OK REVISED PLANS |
|
08/18/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK TO TILE 2) WAITING ON REVISED LIGHTING PLANS |
|
08/15/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) SUPPORT WIRES TO BE AS PER 300.11 ATTACHED AT BOTH ENDS 2) FINISH PREVIOUS ITEMS |
|