Permit: T05CM02886

Parcel: 14118001D


Addresses:

10220 E REES LP


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T05CM02886

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/17/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
AIR BALANCE QUANTITIES ARE ACCEPTABLE
OK FOR FINAL
11/07/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
RELOCATE SPRINKLER PIPE BLOCK ACCESS TO F-2 FURNACE.
PROVIDE PLUGS IN UNUSED CONDENSATE DRAIN OUTLETS.
FINISH INSTALLING EXHAUST FAN IN KITCHEN.
INSTALL OVERFLOW SENSORS.
LABEL ALL CONDENSORS
DETECTORS 91, 10 NOT TESTED