Permit: T05CM02886

Parcel: 14118001D


Addresses:

10220 E REES LP


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T05CM02886

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/21/2006 MECHANICAL - INTERMEDIATE Approved
08/02/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
CHECKED REFER LINES
OK TO INSULATE
07/18/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/27/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO SHEET ROCK CLASSROOMS AND OFFICE NORTH AND SOUTH SIDES OF BLDG
2) CONFIRMED KITCHEN WALL FRAMED WITH METAL
3) RELOCATE 2 SPRINKLERS-BLOCKING ACCESS TO FAN COILS
06/21/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
RELOCATE SPRINKLER PIPES FROM BLOCKING ACCESS TO FAN COILS.
REFER LINE INSTALLATION OK SOUTHSIDE.
06/07/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
- REMOVE INSULATION FROM ENTRY WAYS. MECH. INSTALLER - NEEDS TO FINISH WORK.
- SUSPENDED ROUGH DUCT OK FOR INSULATION.
- TYPE 1 HOOD MUST HAVE MIN. 18" CLEARANCE FROM COMBUSTIBLE CONSTRUCTION.
- REVISE PLANS & RE-SUBMIT IF NECESSARY.
- PROVIDE SECONDARY DRAINS TO A CONSPICUOUS LOCATION OR PROVIDE SENSORS.