Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T05CM02886
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2006 | MECHANICAL - INTERMEDIATE | Approved | ||
| 08/02/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CHECKED REFER LINES OK TO INSULATE |
|
| 07/18/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 06/27/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TO SHEET ROCK CLASSROOMS AND OFFICE NORTH AND SOUTH SIDES OF BLDG 2) CONFIRMED KITCHEN WALL FRAMED WITH METAL 3) RELOCATE 2 SPRINKLERS-BLOCKING ACCESS TO FAN COILS |
|
| 06/21/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RELOCATE SPRINKLER PIPES FROM BLOCKING ACCESS TO FAN COILS. REFER LINE INSTALLATION OK SOUTHSIDE. |
|
| 06/07/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - REMOVE INSULATION FROM ENTRY WAYS. MECH. INSTALLER - NEEDS TO FINISH WORK. - SUSPENDED ROUGH DUCT OK FOR INSULATION. - TYPE 1 HOOD MUST HAVE MIN. 18" CLEARANCE FROM COMBUSTIBLE CONSTRUCTION. - REVISE PLANS & RE-SUBMIT IF NECESSARY. - PROVIDE SECONDARY DRAINS TO A CONSPICUOUS LOCATION OR PROVIDE SENSORS. |