Inspection Status: Approved
Inspection History: PLUMBING - PROGRESS
Permit Number - T05CM02886
Inspection Description - PLUMBING - PROGRESS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/31/2006 | PLUMBING - PROGRESS | Approved | IVRS - Inspection :* | |
| 05/31/2006 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 05/23/2006 | PLUMBING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* PLEASE CALL IN 03057 & 03040 VENTS IN RESTROOM (GANG STYLE) TO BE PER APPROVED PLAN. 1. SUPPORT ALL OVERHEAD HORIZONTAL ABS AT 4' INTERVALS. 2. SUPPORT WATER PIPING AT 6' INTERVALS. 3. PROVIDE CLEANOUTS FOR URINALS. 4. PROVIDE SHOCK STOP FOR SELF CLOSING VALVES OR AIR CHAMBERS. 5. PROVIDE MID-SPAN SUPPORT ON VERTICAL COPPER PIPING IN WALL. 6. COMPLETE INSTALL OF TRAP PRIMERS & PIPING. 7. PROVIDE LONG RADIUS DRAINAGE FITTINGS FOR HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION AND CORRECT FIGURE FITTING AT KITCHEN DRAIN. 8. PROVIDE CORRECT DEVICES & FASTENERS FOR ALL OVERHEAD HANGERS SEE SPEC. SECTION 15101 2.2 9. T&P DRAIN SHALL BE GRAVITY TO DAYLIGHT OR APPROVED INDIRECT RECEPTOR. 10. STAND PIPE RECEPTOR DETAIL F PAGE P3.1 DOES NOT MEET MINIMUM REQUIREMENTS OF 2003 UPC FOR CORRECT RECEPTOR FOR INDIRECT WASTE. FLOOR SINK OR FLOOR DRAIN WITH FUNNEL WOULD BE CORRECT. THESE DEVICES SHALL HAVE TRAP PRIMERS TO PROTECT AGAINST UNSANITARY CONDITION. |