Permit: T05CM02886

Parcel: 14118001D


Addresses:

10220 E REES LP


Inspection Status: Approved

Inspection History: PLUMBING - PROGRESS

Permit Number - T05CM02886

Inspection Description - PLUMBING - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
10/31/2006 PLUMBING - PROGRESS Approved IVRS - Inspection :*
05/31/2006 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
05/23/2006 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection :*
PLEASE CALL IN 03057 & 03040
VENTS IN RESTROOM (GANG STYLE) TO BE PER APPROVED PLAN.
1. SUPPORT ALL OVERHEAD HORIZONTAL ABS AT 4' INTERVALS.
2. SUPPORT WATER PIPING AT 6' INTERVALS.
3. PROVIDE CLEANOUTS FOR URINALS.
4. PROVIDE SHOCK STOP FOR SELF CLOSING VALVES OR AIR CHAMBERS.
5. PROVIDE MID-SPAN SUPPORT ON VERTICAL COPPER PIPING IN WALL.
6. COMPLETE INSTALL OF TRAP PRIMERS & PIPING.
7. PROVIDE LONG RADIUS DRAINAGE FITTINGS FOR HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION AND CORRECT FIGURE FITTING AT KITCHEN DRAIN.
8. PROVIDE CORRECT DEVICES & FASTENERS FOR ALL OVERHEAD HANGERS SEE SPEC. SECTION 15101 2.2
9. T&P DRAIN SHALL BE GRAVITY TO DAYLIGHT OR APPROVED INDIRECT RECEPTOR.
10. STAND PIPE RECEPTOR DETAIL F PAGE P3.1 DOES NOT MEET MINIMUM REQUIREMENTS OF 2003 UPC FOR CORRECT RECEPTOR FOR INDIRECT WASTE. FLOOR SINK OR FLOOR DRAIN WITH FUNNEL WOULD BE CORRECT. THESE DEVICES SHALL HAVE TRAP PRIMERS TO PROTECT AGAINST UNSANITARY CONDITION.