Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T05CM02886
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/31/2006 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 03/08/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* PROVIDE VACUUM BREAKER ON TEMP. HOSE BIBBS |
|
| 03/03/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1) PIPE WRAPS OK |
|
| 03/02/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
| 02/10/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* WATER TEST EAST 4" BUILDING DRAINAGE OK ALL INTERIOR ROUGH SOIL WATER TEST OK 1. NEED TO SEE PIPE WRAPS PRIOR TO CONCRETE AND INSTALL OF TRAP PRIMER TO FLOOR DRAINS. |
|
| 02/09/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* WATER TEST WEST 3" BUILDING DRAIN OK PROVIDE RODLING FOR ADDITION OF (2) 2" BRACH DRAINS FOR MEZZANINE EQUIP. WITH CITY APPROVED PLAN TO FOLLOW 1. WILL NEED TO SEE CONTINUATION OF TRACER WIRE FROM BUILDING SEWER & CONNECTION TO BUILDING SEWER CENTER 4" BUILDING DRAIN WATER TEST UNDERGROUND OK 1. PROVIDE CONTINUATION OF TRACER WIRE ON SEWER UP TO BUILDING. EAST 4" BUILDING DRAIN UNDERGROUND SHALL REQUIRE DIRECTIONAL DRAINAGE FITTINGS FOR DOUBLE WYE USED IN HORIZONTAL LOCATION FOR LAV DRAINAGE. DOUBLE WYE IS VERTICAL DRAINAGE ONLY. PROVIDE CONVENTAL VENTING FOR STOOL IN RESTROOM 126 OR LONG RADIUS FITTINGS FOR VENT BROW FLOOD RIM OF FIXTURE -- PROVIDE SHAPING ON ALL PIPING FOR INSPECTION. |