Permit: T05CM02886

Parcel: 14118001D


Addresses:

10220 E REES LP


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T05CM02886

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
10/31/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
03/08/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
PROVIDE VACUUM BREAKER ON TEMP. HOSE BIBBS
03/03/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) PIPE WRAPS OK
03/02/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
02/10/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
WATER TEST EAST 4" BUILDING DRAINAGE OK
ALL INTERIOR ROUGH SOIL WATER TEST OK
1. NEED TO SEE PIPE WRAPS PRIOR TO CONCRETE AND INSTALL OF TRAP PRIMER TO FLOOR DRAINS.
02/09/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
WATER TEST WEST 3" BUILDING DRAIN OK
PROVIDE RODLING FOR ADDITION OF (2) 2" BRACH DRAINS FOR MEZZANINE EQUIP. WITH CITY APPROVED PLAN TO FOLLOW
1. WILL NEED TO SEE CONTINUATION OF TRACER WIRE FROM BUILDING SEWER & CONNECTION TO BUILDING SEWER CENTER 4" BUILDING DRAIN WATER TEST UNDERGROUND OK
1. PROVIDE CONTINUATION OF TRACER WIRE ON SEWER UP TO BUILDING.
EAST 4" BUILDING DRAIN UNDERGROUND SHALL REQUIRE DIRECTIONAL DRAINAGE FITTINGS FOR DOUBLE WYE USED IN HORIZONTAL LOCATION FOR LAV DRAINAGE. DOUBLE WYE IS VERTICAL DRAINAGE ONLY. PROVIDE CONVENTAL VENTING FOR STOOL IN RESTROOM 126 OR LONG RADIUS FITTINGS FOR VENT BROW FLOOD RIM OF FIXTURE -- PROVIDE SHAPING ON ALL PIPING FOR INSPECTION.