Permit: T05CM02886

Parcel: 14118001D


Addresses:

10220 E REES LP


Inspection Status: Approved

Inspection History: STEM WALL/RETAINING WALL

Permit Number - T05CM02886

Inspection Description - STEM WALL/RETAINING WALL

Inspection Status - Approved

Date Description Inspector Results Comments
11/21/2006 STEM WALL/RETAINING WALL Approved IVRS - Inspection :*
03/11/2006 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
STEM WALLS FOR ALL MECHANICAL YARDS EXCEPT N.W MECH. YARD; ENTIRE SITEWALL & SOUTH TRAIN ENCLOSURE OK
- PLEASE PROVIDE PROPER CLEARANCES AROUND DRAIN LINES @ STEM WALLS.
02/08/2006 STEM WALL/RETAINING WALL Not ready for Inspection IVRS - Inspection :*CONTRACTOR CALLED FOR STEM WALLS @ NEW SHED ( TO5CM0288?) STEM WALL OK-W/L AGAIN FOR THAT ACTIVITY NUMBER UNDER 1015
02/02/2006 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
FOOTING FOR EAST SITE WALL
01/24/2006 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1) ALL PERIMETERS OK