Inspection History: REINFORCED MASONRY PRE-GROUT

Permit Number - T05CM02882

Inspection Description - REINFORCED MASONRY PRE-GROUT

Inspection Status - Approved

Date Description Inspector Results Comments
11/02/2005 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
09/23/2005 REINFORCED MASONRY PRE-GROUT Partial Approval
09/19/2005 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BOND BEAM NOT COMPLETE
2) REBAR NOT AT 48" OC, EXPOSE AT BOTTOM
3) CELLS GROUTED BEFORE FIRST LEFT INSPECTION
09/16/2005 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FIRST LIFT GROUTED BEFORE INSPECTION APPROVAL
2) PROVIDE PACHOMETER TEST