Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 09/18/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO TILE |
|
| 09/15/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) NEED REJECTION PINS AND FUSES 2) SERVICE FOR 7137 OK 3) FINISH #2 PREVIOUS INSPECTION |
|
| 09/13/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) FIXTURES TO BE SUPPORTED TO GRID. IF MANUFACTURERS CLIPS ARE USED THEY NEED TO BE EFFECTIVE 410.16 2) MANUFACTURER WIRING TO BE SUPPORTED AS PER 300.11 AND 604.6 (E), 110.3 AND 330.30 3) VDV CABELING TO BE AS PER 725.6 AND 800.6 4) BOXES IN CEILING NEED SUPPORT WIRES 5) M/C CABLE TO BE TERMINATED 6) FINISH SUPPORT WIRES TO FIXTURES 7) REMOVE ABANDONED NM CABLE 8) CAP UNUSED RELOCK ENDS |