Permit: T05CM02840

Parcel: 141011150

Inspection Status: Approved

Inspection History: STUCCO MESH

Permit Number - T05CM02840

Inspection Description - STUCCO MESH

Inspection Status - Approved

Date Description Inspector Results Comments
07/29/2005 STUCCO MESH Approved IVRS - Inspection :*
07/14/2005 STUCCO MESH Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WEEP SCRRED TO BE 4" ABOVE GRADE, BUT MUST COVER FOUNDATION LINE WITH THE 3 1/2" FLANGE, OVERSIZED WEEP SCREED
2) USED WRONG SIZED, STAPLES, MUST PENETRATE WOOD, MINIMUM OF 1 3/4" VERT. CENTERS FOR STUDS, 6" ON CENTER FOR STAPLES CENTERS
3) LATH NOT COMPLETED, IS YOUR WIRE REINFORCING SELF-FURRED BATH OR CHICKEN WIRE ?, I TOOK A SAMPLE TO COMPARE
4) CONCRETE SLAB IS TO LOW TO GRADE
5) BOTTOM PLATES TO ANCHORED WITH 1/2 DIAMETER A.B. AT 6" ON CENTER PER CODE
6) NO MECH TIE-NEW FRAMING TO OLD ROOF
7) B. BOARD HTR. TO BE ON SEPERATE CIRCUIT/SPLIT BREAKER 2-20 AMP OK
8) WHERE DOES ELECTRIC HOME RUN ORIGINATE
9) DOES THIS ROOM RETSRICT EMERGENCY EGRESS ? FROM BEDROOM WINDOW NORTH WALL