Inspection History Details
Inspection Status: Approved
Inspection History: STUCCO MESH
Permit Number - T05CM02840
Inspection Description - STUCCO MESH
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/29/2005 | STUCCO MESH | Approved | IVRS - Inspection :* | |
07/14/2005 | STUCCO MESH | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WEEP SCRRED TO BE 4" ABOVE GRADE, BUT MUST COVER FOUNDATION LINE WITH THE 3 1/2" FLANGE, OVERSIZED WEEP SCREED 2) USED WRONG SIZED, STAPLES, MUST PENETRATE WOOD, MINIMUM OF 1 3/4" VERT. CENTERS FOR STUDS, 6" ON CENTER FOR STAPLES CENTERS 3) LATH NOT COMPLETED, IS YOUR WIRE REINFORCING SELF-FURRED BATH OR CHICKEN WIRE ?, I TOOK A SAMPLE TO COMPARE 4) CONCRETE SLAB IS TO LOW TO GRADE 5) BOTTOM PLATES TO ANCHORED WITH 1/2 DIAMETER A.B. AT 6" ON CENTER PER CODE 6) NO MECH TIE-NEW FRAMING TO OLD ROOF 7) B. BOARD HTR. TO BE ON SEPERATE CIRCUIT/SPLIT BREAKER 2-20 AMP OK 8) WHERE DOES ELECTRIC HOME RUN ORIGINATE 9) DOES THIS ROOM RETSRICT EMERGENCY EGRESS ? FROM BEDROOM WINDOW NORTH WALL |