Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/31/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/30/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NEED SWITCHED OUTLET OR LIGHT FIXTURE (WORKING) IN EACH HABITABLE ROOM PER NEC 210.70 |
|
| 03/23/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. STILL NEED TO COMPLETE CORRECTIONS #4, #7, #8 FROM PREVIOUS INSPECTION. |
|
| 03/13/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/10/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. OUTLET BOXES IN CABINETS TO BE FLUSH WITH SURFACE 2002 NEC 314.20 2. INSTALL ANTI-TIP BRACKET ON RANGES NEC 110.3 (B) 3. ALL SWITCHES NEED EQUIPMENT GROUND CONNECTED TO THEM NEC 404.9 (B) - HAVE COVERS OFF NEXT INSPECTION. 4. NEED LIGHT OR SWITCHED OUTLET IN FAMILY ROOM NEC 210.70 5. TIGHTEN ALL LOOSE OUTLETS - SECURE TO WALL NEC 406.4(A) 6. MASTER BATH LIGHT SWITCH UPSIDE DOWN NEC 110.3(B) 7. BEDROOMS NEED LIGHT OR SWITCHED OUTLETS NEC 210.70 8. MAKE A.C. DISCONNECTS AND OUTLETS SECURE 110.13(A) UNIT 1 INSPECTION ONLY CHECK FOR BOTH UNITS 9. INSTALL EXTERIOR LIGHT FIXTURES AND BULBS NEC 210.70 (2) |