Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/28/2005 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :*OK TO COVER ELECTRICAL IN CEILINGS AND WALLS. OK TO ENERGIZE SERVICE | |
| 12/23/2005 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The service is not per code.| 210* |
|
| 12/21/2005 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The service is not per code.| 210* |
|
| 12/19/2005 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The service is not per code.| 210*INSTALL PROPER CONNECTOR AND GROUNDING BUSHING ON SERVICE RISER INSTALL GROUNDING ELECTRODE TO SERVICE INSTALL ADDRESS ON SERVICE SEAL FEEDER OPENINGS ON BOTH ENDS GROUND METAL BOX'S AND ADD NAIL PLATES OK TO START INSULATION |
|
| 12/16/2005 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The service is not per code.| 210* |
|
| 08/25/2005 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* |