Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T05CM02836
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/12/2007 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
07/11/2007 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1) MISSING PERMIT TO SIGN OFF ON RE-CALL SO I CAN SIGN PERMIT AND GATHER UP BLDG CERTS 11:10 AM |
|
07/10/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PAINT ALL ABS VENT STACKS THROUGH ROOF-TO PROTECT FROM SUN 2) SMOKIE NOT WORKING |
|
07/06/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) IDENTIFY AIR CONDENSOR TO PROPERLY SIZED FUSES 2) NEED BUBBLE COVER GFCI OUTLET WEST SIDE OF HOUSE 3) HOSE BIB NEEDS ANTI-SIPHON 4) EXTEND CONDENSATION DRAIN ? ABOVE GROUND 5) MISSING OUTLET IN HALLWAY 6) BEDROOM AND SMOKIES NEED ARC-FAULT BREAKERS 7) SEAL AROUND BASE OF TOILET 8) STOVE MISSING ANTI-TIP DEVICE 9) OUTLET COVERS MUST BE ON WALL FOR FINAL INSPECTION 10) MISSING TRACER WIRE YARD WATER |