Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T05CM02798
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/14/2005 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* 1) OK FOR SHEETROCK 2) PROVIDE BACKING AROUND CEILING BOXES 3) DUCT LINER INSIDE BLDG ENVELOPE REQUIRED TO BE R-5 4) 1" LINER IS R4.2, 1/2" LINER R-2 5) PROVIDE ADEQUATE INSULATION 6) PLANS MAY HABE BEEN APPROVED IN ERROR 7) ITEM 04005 NOT APPLICABLE PER PAPERWORK TURNED IN BY INSPECTOR J. MILITELLO |