Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM02795
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/19/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/18/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NOTE #3 LAST INSP. NOT DONE |
|
08/17/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
08/09/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT 1 1/2"-3/4" AND 1" CONDUITS AROUND ELECTRICAL SERVICE AREA AND ROOF 2) ID CIRCUIT BREAKERS IN ALL PANELS 3) COVERS TO MAIN BREAKERS AT SERVICE NEED TO BE REPAIRED, ONE MISSING 4) ISOLATE GROUND AND NEUTRAL BARS IN PANEL #2 5) RE-ROUTE NEUTRAL AND GROUND FOR PANEL #1, NOT TO BE ROUTED THRU PANEL #3 6) VERIFY ELECTRICAL CONTR. DOING WORK LICENSE NUMBER AND PHONE NUMBER |
|
08/05/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) COMPLETE WIRING AT WATER HEATER ROOM 2) UNITS 2 AND 3 LOCKED 3) ALL TENANTS MUST HAVE ACCESS TP SERVOCE DISCONNECTS, NO LOCKED GATES, OR FENCE THAT MAY DENIE ACCESS IN AN EMERGENCY |