Permit: T05CM02790

Parcel: 11015123B


Addresses:

5563 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM02790

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/21/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
07/14/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
04/05/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK WALLS SUBJECT TO LETTER.
04/03/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. TIGHTEN LOOSE FITTINGS.
2. PLEASE PROVIDE A LETTER AUTHORIZING USE OF M/C CABLE AND DIE CAST FITTINGS AS PER PLAN SPEC'S
3. WILL NEED ACCESS TO SEE RUN INSIDE OF MAIN BUILDING.